Fix battery sign and separate PV from inverter output
Verified against simultaneous SolarEdge app readings (PV 40 W, battery discharge 520 W, house 560 W): battery1_power negative means discharge, and power_ac on this DC-coupled Energy Hub is the inverter's TOTAL AC output - it already contains the battery contribution. The old formula double-counted the battery, so house_load collapsed (44 W shown vs 560 W real) and the PV tile showed battery-inflated totals, which looked like PV and house consumption were swapped. New derived fields: house_load = power_ac + grid, and pv_power = power_ac - battery (true PV production). Dashboard PV tiles and both yield panels now use pv_power / integral(pv_power) - the energy_total lifetime counter also counts battery throughput and is not a PV yield.
This commit is contained in:
4 files changed
+57
-42
No files matched your search
@@ -56,15 +56,18 @@ Import `grafana_dashboard.json` (Dashboards -> New -> Import). Select your
|
||||
InfluxDB datasource when prompted (e.g. `InfluxDB-HJK`); the `$serial` variable
|
||||
is filled from the `serialnumber` tag. InfluxQL only, InfluxDB 1.x.
|
||||
|
||||
The daemon also writes derived flow fields (`house_load`, `grid_import`,
|
||||
`grid_export`, `battery_charge`, `battery_discharge`, `solar_to_house`) so the
|
||||
dashboard's consumption-source panels are plain `mean()`/`integral()` queries.
|
||||
The daemon also writes derived flow fields (`house_load`, `pv_power`,
|
||||
`grid_import`, `grid_export`, `battery_charge`, `battery_discharge`,
|
||||
`solar_to_house`) so the dashboard's consumption-source panels are plain
|
||||
`mean()`/`integral()` queries.
|
||||
|
||||
**Sign calibration:** `meter1_power` positive = import and `battery1_power`
|
||||
positive = discharge are assumptions observed once; verify on the first sunny
|
||||
day (export while surplus / charge while battery fills). If inverted, flip
|
||||
`METER_IMPORT_POSITIVE` / `BATTERY_DISCHARGE_POSITIVE` in
|
||||
`solaredge_modbus_mqtt/__init__.py` and restart - all derived fields follow.
|
||||
**Sign conventions (verified against the SolarEdge app):** `meter1_power`
|
||||
positive = export, `battery1_power` negative = discharge, and `power_ac` is
|
||||
the inverter's *total* AC output (PV + battery, DC-coupled Energy Hub) - which
|
||||
is why `pv_power = power_ac - battery` and `house_load = power_ac + grid`.
|
||||
If a different system disagrees, flip `METER_IMPORT_POSITIVE` /
|
||||
`BATTERY_DISCHARGE_POSITIVE` in `solaredge_modbus_mqtt/__init__.py` and
|
||||
restart - the derived fields follow.
|
||||
|
||||
|
||||